EICR Certificate Generator/ guides / Zs values

Maximum Zs values — lookup table

Maximum permitted earth-fault loop impedance (Zs) for final circuits at 230 V with the BS 7671:2018+A2:2022 voltage factor Cmin = 0.95 — the U0 × Cmin ÷ Ia method for B, C and D type MCBs.

How the table is built

For a circuit-breaker, the maximum Zs = U0 × Cmin ÷ Ia, where Ia is the current causing the protective device to operate within the required disconnection time (0.4 s for final circuits ≤ 63 A in TN systems). For MCBs to BS EN 60898: type B trips at 5×In, type C at 10×In, type D at 20×In. With U0 = 230 V and Cmin = 0.95, the numerator is 218.5 V.

RatingType B (max Zs)Type C (max Zs)Type D (max Zs)
6 A7.28 Ω3.64 Ω1.82 Ω
10 A4.37 Ω2.19 Ω1.09 Ω
16 A2.73 Ω1.37 Ω0.68 Ω
20 A2.19 Ω1.09 Ω0.55 Ω
25 A1.75 Ω0.87 Ω0.44 Ω
32 A1.37 Ω0.68 Ω0.34 Ω
40 A1.09 Ω0.55 Ω0.27 Ω
50 A0.87 Ω0.44 Ω0.22 Ω

Reading the results on a schedule

RCD-only fault protection (typical TT)

Where an RCD is the fault-protection device rather than the MCB, the maximum Zs is 50 V ÷ IΔn: about 1,667 Ω for a 30 mA RCD. That is why TT installations with high electrode resistance can still comply — but the report must also carry the RCD's operating time at IΔn, and disconnection-time compliance is checked against the RCD, not the breaker.

Recording Zs correctly on the schedule of test results — device type, rating, measured value and the tabulated maximum — is one of the details that separates a defensible report from a rubber-stamped one. See the red-flags guide. The generator carries a full per-circuit schedule with Zs, RCD times and AFDD columns.